The innovative Eurotherm 3216 controller offers precision control of temperature and other process variables together with a host of advanced features not normally found in this class of controller. The emphasis is on simplicity and ease of use. A simple 'QuickStart' code can be used to configure all the essential functions, including input sensor type, measurement range, control options and alarms - making 'Out of the Box' operation truly achievable.
The controller can have up to 4 software alarms, which include absolute high & low, deviation high, low or band & rate of change, that are auto or manual latching, non-latching or event only, and up to four conditions can be assigned to one output.
An internal timer is configurable as an interval timer or delay timer; for example it can dwell when the setpoint is reached or provide a soft start for hot runner control.
The Contact Input can function as alarm acknowledge, SP2 select, manual, keylock, timer functions, standby select, RSP select.
The 2-wire Comms Model additonally feautres 2-wire RS-485 Modbus communication and an additional Logic input.
- Quick and easy commissioning with one shot auto-tuning.
- Easy, comprehensive operator information.
- 4 Alarms.
- Internal Timer.
- IP65 (NEMA 4X) rated front panel.
Sensor Input: Thermocouple, RTD, Linear milliamps, Linear volts, millivolts, Contact Input (instead of Logic output)
Thermocouple: Type B, C, J, K, L, N, R, S, T
RTD: 2 or 3-wire PT100
Linera milliamps: 0 - 20mA, 4 -20mA - by fitting 2.49 Ohm external shunt (supplied)
Linear Volts: 0 - 10V - by fitting 100K Ohm/806 Ohm external divider module (not supplied)
millivolts: 0 - 80mV
Contact Input (instead of Logic output): Open >500Ω, closed <150Ω
Outputs: Standard, Programmer & Comms Models: 1x Logic (SSR) 12Vdc, 1x Relay - Form A (normally open) (Min 100mA@12vdc, max 2A@264Vac resistive)
Extra C/O Relay Model (Only): Also has Change-over Relay - Form C (Min 100mA@12vdc, max 2A@264Vac resistive)
Logic/4-20mA Model (Only): 1x Logic (SSR) 12Vdc, 1x 4-20mA/0-20mA analogue
Supply Voltage: 100 to 240Vac, -15%, +10%, 48 to 62 Hz, max 6W
Dimensions (Overall): 48 x 48 x 101mm (WxHxD)
Depth behind panel: 90mm
Panel Mounting: 1/16 DIN, 45 x 45mm (WxH) panel cut-out
Eurotherm 3200 Series DatasheetThese units are part of a wider range, see the whole range.